Products
Steam Boiler/ Hot Water Boiler/ Water Tube Boiler/ Vacuum Boiler/ Ultraten Boiler / Low Nox Boiler /
  • WATER TUBE BOILER
  • WATER TUBE BOILER

Water Tube Boiler

Product Category : Water Tube Boiler

1. It adopts double longitudinal drums in “D” arrangement, full water membrane wall structure, and micro-positive chamber combustion.

2. The boiler is in an integral type or module type rapid assembly structure, with characteristics of compact structure, less land occupation, small field work quantity and short installation period.

3. The combustion system has good air-fuel ratio, which makes the boiler keep operating at optimum combustion state, with advantage of power saving and environmental protection.

 

Tel:+86-372-3383152 E-mail:lx@fangkuai.com
Follow Us:
product description

1. It adopts double longitudinal drums in “D” arrangement, full water membrane wall structure, and micro-positive chamber combustion.

2. The boiler is in an integral type or module type rapid assembly structure, with characteristics of compact structure, less land occupation, small field work quantity and short installation period.

3. The combustion system has good air-fuel ratio, which makes the boiler keep operating at optimum combustion state, with advantage of power saving and environmental protection.

Rated evaporation rate of saturated steam boiler: 10-40t/h

Rated evaporation rate of superheated steam boiler: 10-40t/h

Rated heat-power of hot water boiler: 10.5-29MW

Rated evaporation rate of large bulk water pipe boiler: 35-130 t/h

Performance advantages

Technical Parameters

BoilerType Unit SZS10-1.6/350-Y(Q) SZS15-1.6/350-Y(Q) SZS20-2.5/400-Y(Q) SZS25-2.5/400-Y(Q)
Rated Steam Output  t/h 10 15 20 25
Feed water pump electric power KW 18.5 37 55 90
Fan electric power KW 22 37 55 75
Fuel consumption diesel Kg/h 711.8 1067.7 1475.1 1844.2
heavy oil Kg/h 740 1109.9 1533.7 1917.1
NG Nm^3/h 752.2 1128.3 1559.1 1948.9
City Coal Gas   Nm^3/h 1527.8 2291.7 3166.7 3958.3
LNG Nm^3/h 275 412.5 570 712.6
Gas pressure  NG mmH2O 1500-3000 2000-3000 2000-3000 3000-20000
City Coal Gas   mmH2O 1500-3000 2000-3000 2000-3000 3000-20000
LNG mmH2O 2000-3000 3000-4000 3000-4000 5000-20000
Transportation dimension Length mm 8120 9350 9700 10200
Width  mm 3410 4390 4140 4140
Height mm 3750 3770 4350 4350
Installation dimension Length mm 10250 11330 11720 12520
Width  mm 6570 6750 7280 7180
Height mm 4680 4780 5180 5180
Transportation  Weight t 38 40 62 65
Feed Water Inlet PN MPa 2.5 4
DN MPa 50 65 65 80
Main Steam Outlet PN mm 2.5 4
DN MPa 150
Vice Steam Outlet PN MPa 2.5 4
DN mm 40
Manual blowdown PN MPa 2.5 4
DN mm 50
Continuous blowdown PN MPa 2.5 4
DN mm 40
Safety Valve nozzle PN MPa 2.5 4
DN mm 80 100 150
Chimney  mm 650*650 1000*850 1650*640 1650*675
Rated Steam Pressure MPa 1.6 2.5
Rated superheated Steam Pressure 350 400
General Electric V/Hz 380/50 Combustion Mode MPa Micro-positive Chamber Combustion
Efficiency % 100-104 Combustion Adjustment MPa Full Auto Ratio Control

 